Q.The combination of AZ Series EtherCAT compatible driver and OMRON Corporation PLC is controlled using the internal profile of the driver. How do I perform push-motion return-to-home?

A.

Target Products

AZ Series EtherCAT Compatible Driver:
AZD-AED, AZD-CED, AZD-KED, AZD2A-KED, AZD2B-KED, AZD3A-KED, AZD4A-KED, AZD-KRED

Control Methods: Use the Internal Profile of Driver (Operation mode PP, PV, HM mode)

When using PLC motion control (Operation mode CSP, CSV mode), please check the FAQ here.

Follow the procedure below to change the settings and execute return-to-home.

Set "Homing Method (6098h)" to "Return-to-Home operation of our specifications".
MEXE02_parameter1
Set "(HOME) Home-seeking mode (4160h)" to "Push-motion".
Set "JOG/HOME/ZHOME operation setting (47F5h)" to "Manual setting".
MEXE02_parameter2

After the setting is completed, when return-to-home is executed in homing mode (HM), push-motion return-to-home is started. The execution of push-motion return-to-home is controlled by the Controlword (6040h).

Controlword for homing mode

Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
Manufacturer specific (ms) Reserved oms Halt
- - - - - -
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Fault
reset
Operation mode specific (oms) Enable
operation
Quick
stop
Enable
voltage
Switch
on
- - Homing
operation
start

The execution procedure is as follows.

  1. Set the Modes of operation (6060h) to the homing mode, "6: Homing mode (HM)"
  2. Turn Bit 2 (Quick stop) and Bit 1 (Enable voltage) of the Controlword ON
  3. Turn Bit 3 (Enable Operation) and Bit 0 (Switch on) of the Controlword ON (it becomes the excitation state)
  4. Turn Bit 4 (Homing Operation start) of the Controlword ON to start return-to-home

[Supplement]
For Oriental Motor electric actuators, Maximum pushing return-to-home speed and Maximum push current are respectively determined for each product.
You can check the electric actuator information on the "Unit information monitor" of the support software MEXE02.

MEXE02_parameter3

When setting the parameter for Speed during search for zero (6099h-02h) and (HOME) Operating current for push-home-seeking, do not set values that exceed the Maximum pushing return-to-home speed and Maximum push current.
If you configure the setting that exceeds the Maximum pushing return-to-home speed or Maximum push current, an "Operation data error" alarm will trigger at start.

MEXE02_parameter4
MEXE02_parameter5

Related Information: AZ Series EtherCAT Compatible Driver FAQ

Product Category: αSTEP, network compatible products and controllers, electric actuators
Model and Series: AZ Series, electric actuator AZ Series equipped
Description: How to Use/Setting Method
FAQ No.: 579