αSTEP/Stepper Motor αSTEP/Inrush Current (Reference value) of Stepper Motors

Generally, a circuit breaker (wiring circuit breaker) is used to prevent overcurrent from flowing due to a wiring short circuit or other factor.
When selecting a breaker, reference the "inrush current" values below, and "input current" values listed on the product details page, or catalog specifications.

αSTEP

Series Power Supply Voltage [V] Inrush Current [A]
At Power ON After 20 ms
AZ Series Single-Phase 100-120 19 11
Single-Phase 200-240 37 8
Three-Phase 200-240 37 3
AR Series Single-Phase 100-115 19 11
Single-Phase 200-230 37 8
Three-Phase 200-230 37 2

Stepper Motors

Series Power Supply Voltage [V] Inrush Current [A]
At Power ON After 20 ms
RKII Series Single-Phase 100-120 19 11
Single-Phase 200-240 37 7

Related Information: Values when selecting circuit breakers to combine with AC motors