Q.The combination of AZ Series EtherCAT compatible driver and OMRON Corporation PLC is controlled using MC commands. How many motor resolutions should I set in the axis settings? How should I set the mm or deg setting?

A.

Applicable Products

AZ Series EtherCAT Compatible Driver:
AZD-AED, AZD-CED, AZD-KED, AZD2A-KED, AZD2B-KED, AZD3A-KED, AZD4A-KED, AZD-KRED

Control Methods: Use the motion control (MC command) of PLC (Operation mode CSP, CSV mode)

If you would like to use the internal profile of the driver (Operation mode PP, PV, HM mode), check the FAQ here.

The initial value of the resolution is 10,000 P/R.
Set 10,000 P/R for the motor resolution (the number of pulses per motor revolution) set in Sysmac Studio - axis settings by OMRON Corporation. The resolution setting of the driver can be changed, but Oriental Motor recommends using the initial value when using the MC command. If this is changed, vibration may be increased.

OMRON Setting Screen 1

If you would like to configure mm or deg settings, leave the resolution setting at 10,000 P/R and set mm or deg in the axis setting of Sysmac Studio by OMRON Corporation.

Setting examples of Oriental Motor's electric actuators (electric linear slides, electric cylinders, compact electric cylinders) are shown below.

OMRON Setting Screen 2

Product Category: αSTEP, Network compatible products and controllers, Electric actuators
Model and Series: AZ Series, Electric actuators AZ Series equipped, Hollow rotary actuators
Description: How to Use/Setting Method
FAQ No.: 590

Related FAQs


Email to Technical Support

After opening the email, we will check the contents and contact you. Please note that depending on the nature of your enquiry, we may contact you by phone.

Has your question been resolved?

If you have any other comments or requests, please enter them here.

  • *We will not be able to respond to the information you have entered.